EVOLUTION: RAIL INSTALLATION INSTRUCTIONS


          1.   When rails are mounted in accordance to manufacturer’s installation instructions, rail shall accommodate
               function loading up to 62 foot pounds of torque per foot between 16” centers.
          2.   The recommended Evolution Equipment Rail loading should not exceed 20 pounds of weight per linear foot.
          3.   The Evolution Equipment Rail loading capability is as well a function of dry wall load bearing capacity, drywall
               mounting/installation, and quality of installation hardware.
           ** Installer MUST use 1/4” mounting hardware appropriate to wall construction type or to
           the installation method required.
           Contact manufacturer with any  installation questions at (407) 614-8781

           ** Refer to the relevant elevation drawings and other specification documentation for
           quantity and location details for each project.

           Stud Mount
                                        1.   Position and level the “Evolution” rail on the wall at the correct height and
                                             location as shown on the elevation drawings.  Mark location on wall.
                                        2.   Align holes in rail with studs.  If required, drill new holes into rail to align with
                                             stud locations.

                                        3.   Using a 1/4” sheet metal screw, securely fasten the screws through the rail and
                                             drywall and into the studs.  Ensure a tight fit between rail and wall.

                                        4.   Insert supplied inlay strip into grooves and secure end cap.

           Drywall Mount WITH Backing (metal or wood)

           Follow Drywall Mount instructions 1 + 2 below.   Use 1/4” screws to securely mount the rail to the wall.  For sheet
           metal backing use sheet metal screws.  For wood backing, use wood screws.  Ensure a tight fit between rail and wall.
           Finish with inlay strips and secure end cap into position.

           Drywall Mount WITHOUT Backing


                                        1.   Position and level the “Evolution” rail on the wall at the correct height and
                                             location as shown on the elevation drawings.  Mark location on wall.
                                        2.   Mark through each of the pre-drilled holes in the rail onto the drywall.

                                        3.   Remove the rail and securely install 1/4” toggle-type wall anchors in locations as
                                             marked.
                                        4.   Realign the rail holes with the installed wall anchors and tightly secure the rail to
          Wall Anchor types A + B            the wall with the 1/4” wall anchor machine screws.  Ensure a tight fit between
                                             rail and wall.
                                        5.   Insert supplied inlay strip into grooves and secure end cap.